CVE-2011-20002
A vulnerability has been identified in SIMATIC S7-1200 CPU V1 family (incl. SIPLUS variants) (All versions < V2.0.2), SIMATIC S7-1200 CPU V2 family (incl. SIPLUS variants) (All versions < V2.0.2). Affected controllers are vulnerable to capture-replay in the communication with the engineering software. This could allow an on-path attacker between the engineering software and the controller to execute any previously recorded commands at a later time (e.g. set the controller to STOP), regardless whether or not the controller had a password configured.
Published:Oct 14, 2025
Last Modified:Apr 15, 2026
EPS:Oct 14, 2025
EPSS Score:0.00042
CVSS Score:7.4