CVE Feed

    Dashboard / CVE / CVE-2018-4844

    CVE-2018-4844

    A vulnerability has been identified in SIMATIC WinCC OA UI for Android (All versions < V3.15.10), SIMATIC WinCC OA UI for iOS (All versions < V3.15.10). Insufficient limitation of CONTROL script capabilities could allow read and write access from one HMI project cache folder to other HMI project cache folders within the app's sandbox on the same mobile device. This includes HMI project cache folders of other configured WinCC OA servers. The security vulnerability could be exploited by an attacker who tricks an app user to connect to an attacker-controlled WinCC OA server. Successful exploitation requires user interaction and read/write access to the app's folder on a mobile device. The vulnerability could allow reading data from and writing data to the app's folder. At the time of advisory publication no public exploitation of this security vulnerability was known. Siemens confirms the security vulnerability and provides mitigations to resolve the security issue.

    Published:Mar 20, 2018
    Last Modified:Nov 21, 2024
    EPS:Mar 20, 2018
    EPSS Score:0.00132
    CVSS Score:6.7

    Affected Products

    Vendor
    Siemens
    Product
    Simatic Wincc Oa Ui

    Exploits

    No exploit reference

    Common Vulnerability Scoring System

    Attack Vector
    Network
    Adjacent
    Local
    Physical
    Privileges Required
    None
    Low
    High
    User Interaction
    None
    Required
    Scope
    Unchanged
    Changed
    Confidentiality
    None
    Low
    High
    Integrity
    None
    Low
    High
    Availability
    None
    Low
    High