CVE Feed

    Dashboard / CVE / CVE-2022-30319

    CVE-2022-30319

    Saia Burgess Controls (SBC) PCD through 2022-05-06 allows Authentication bypass. According to FSCT-2022-0062, there is a Saia Burgess Controls (SBC) PCD S-Bus authentication bypass issue. The affected components are characterized as: S-Bus (5050/UDP) authentication. The potential impact is: Authentication bypass. The Saia Burgess Controls (SBC) PCD controllers utilize the S-Bus protocol (5050/UDP) for a variety of engineering purposes. It is possible to configure a password in order to restrict access to sensitive engineering functionality. Authentication functions on the basis of a MAC/IP whitelist with inactivity timeout to which an authenticated client's MAC/IP is stored. UDP traffic can be spoofed to bypass the whitelist-based access control. Since UDP is stateless, an attacker capable of passively observing traffic can spoof arbitrary messages using the MAC/IP of an authenticated client. This allows the attacker access to sensitive engineering functionality such as uploading/downloading control logic and manipulating controller configuration.

    Published:Jul 28, 2022
    Last Modified:Nov 21, 2024
    EPS:Jul 28, 2022
    EPSS Score:0.00059
    CVSS Score:8.1

    Affected Products

    Vendor
    Honeywell
    Product
    Saia Pg5 Controls Suite

    Exploits

    No exploit reference

    Related CVEs

    Common Vulnerability Scoring System

    Attack Vector
    Network
    Adjacent
    Local
    Physical
    Privileges Required
    None
    Low
    High
    User Interaction
    None
    Required
    Scope
    Unchanged
    Changed
    Confidentiality
    None
    Low
    High
    Integrity
    None
    Low
    High
    Availability
    None
    Low
    High