CVE Feed

    Dashboard / CVE / CVE-2025-3756

    CVE-2025-3756

    A vulnerability exists in the command handling of the IEC 61850 communication stack included in the product revisions listed as affected in this CVE. An attacker with access to IEC 61850 networks could exploit the vulnera bility by using a specially crafted 61850 packet, forcing the communication interfaces of the PM 877, CI850 and CI868 modules into fault mode or causing unavailability of the S+ Operations 61850 connectivity, resulting in a denial-of-service situation.  The System 800xA IEC61850 Connect is not affected. Note: This vulnerability does not impact on the overall availability and functionality of the S+ Operations node, only the 61850 communication function.     This issue affects AC800M (System 800xA): from 6.0.0x through 6.0.0303.0, from 6.1.0x through 6.1.0031.0, from 6.1.1x through 6.1.1004.0, from 6.1.1x through 6.1.1202.0, from 6.2.0x through 6.2.0006.0; Symphony Plus SD Series: A_0, A_1, A_2.003, A_3.005, A_4.001, B_0.005; Symphony Plus MR (Melody Rack): from 3.10 through 3.52; S+ Operations: 2.1, 2.2, 2.3, 3.3.

    Published:Apr 13, 2026
    Last Modified:Apr 17, 2026
    EPS:Apr 13, 2026
    EPSS Score:0.00023
    CVSS Score:6.5

    Affected Products

    Vendor
    Abb
    Product
    800xa System
    Vendor
    Abb
    Product
    Symphony + Operations
    Vendor
    Abb
    Product
    Symphony Plus Mr (melody Rack)
    Vendor
    Abb
    Product
    Symphony Plus Sd Series

    Exploits

    No exploit reference

    Common Attack Pattern Enumeration and Classification (CAPEC)

    No CAPEC recorded yet

    Common Vulnerability Scoring System

    Attack Vector
    Network
    Adjacent
    Local
    Physical
    Privileges Required
    None
    Low
    High
    User Interaction
    None
    Required
    Scope
    Unchanged
    Changed
    Confidentiality
    None
    Low
    High
    Integrity
    None
    Low
    High
    Availability
    None
    Low
    High