Powertekpdus

    Dashboard / Vendors

    Products: 14
    Vulnerabilities: 2
    Known Exploited: 0
    2
    Critical Level Threats
    0
    High Level Threats
    0
    Medium Level Threats
    0
    Low Level Threats

    Vulnerabilities

    100806040200
    JanFebMarAprMayJunJulAugSepOctNovDec
    Critical Level Threats
    High Level Threats
    Medium Level Threats
    Low Level Threats

    Products Security index

    Actions
    Items Per Page

    Vulnerabilities

    CVE-2022-33174

    Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 allows remote authorization bypass in the web interface. To exploit the vulnerability, an attacker must send an HTTP packet to the data retrieval interface (/cgi/get_param.cgi) with the tmpToken cookie set to an empty string followed by a semicolon. This bypasses an active session authorization check. This can be then used to fetch the values of protected sys.passwd and sys.su.name fields that contain the username and password in cleartext.

    Last Modified: Nov 21, 2024
    Published: Jun 13, 2022

    CVE-2022-33175

    Power Distribution Units running on Powertek firmware (multiple brands) before 3.30.30 have an insecure permissions setting on the user.token field that is accessible to everyone through the /cgi/get_param.cgi HTTP API. This leads to disclosing active session ids of currently logged-in administrators. The session id can then be reused to act as the administrator, allowing reading of the cleartext password, or reconfiguring the device.

    Last Modified: Nov 21, 2024
    Published: Jun 13, 2022