CVE Feed

    Dashboard / CVE / CVE-2018-16556

    CVE-2018-16556

    A vulnerability has been identified in SIMATIC S7-400 CPU 412-1 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-2 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 DP V7 (All versions), SIMATIC S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 414F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416-2 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 DP V7 (All versions), SIMATIC S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 416F-2 DP V7 (All versions), SIMATIC S7-400 CPU 416F-3 PN/DP V7 (All versions < V7.0.3), SIMATIC S7-400 CPU 417-4 DP V7 (All versions), SIMATIC S7-400 CPU 412-2 PN V7 (All versions < V7.0.3), SIMATIC S7-400 H V4.5 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-400 H V6 CPU family (incl. SIPLUS variants) (All versions < V6.0.9), SIMATIC S7-400 PN/DP V6 and below CPU family (incl. SIPLUS variants) (All versions), SIMATIC S7-410 CPU family (incl. SIPLUS variants) (All versions < V8.2.1), SIPLUS S7-400 CPU 414-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 PN/DP V7 (All versions < V7.0.3), SIPLUS S7-400 CPU 416-3 V7 (All versions), SIPLUS S7-400 CPU 417-4 V7 (All versions). Specially crafted packets sent to port 102/tcp via Ethernet interface, via PROFIBUS, or via Multi Point Interfaces (MPI) could cause the affected devices to go into defect mode. Manual reboot is required to resume normal operation. Successful exploitation requires an attacker to be able to send specially crafted packets to port 102/tcp via Ethernet interface, via PROFIBUS or Multi Point Interfaces (MPI). No user interaction and no user privileges are required to exploit the security vulnerability. The vulnerability could allow causing a denial of service condition of the core functionality of the CPU, compromising the availability of the system.

    Published:Dec 13, 2018
    Last Modified:Nov 21, 2024
    EPS:Dec 13, 2018
    EPSS Score:0.00188
    CVSS Score:7.5

    Affected Products

    Vendor
    Siemens
    Product
    Simatic S7-400
    Vendor
    Siemens
    Product
    Simatic S7-400 Firmware
    Vendor
    Siemens
    Product
    Simatic S7-400 Pn\/dp V7
    Vendor
    Siemens
    Product
    Simatic S7-400 Pn\/dp V7 Firmware
    Vendor
    Siemens
    Product
    Simatic S7-400h
    Vendor
    Siemens
    Product
    Simatic S7-400h Firmware
    Vendor
    Siemens
    Product
    Simatic S7-400h V6
    Vendor
    Siemens
    Product
    Simatic S7-400h V6 Firmware
    Vendor
    Siemens
    Product
    Simatic S7-410
    Vendor
    Siemens
    Product
    Simatic S7-410 Firmware

    Exploits

    No exploit reference

    Common Weakness Enumeration

    Common Attack Pattern Enumeration and Classification (CAPEC)

    Common Vulnerability Scoring System

    Attack Vector
    Network
    Adjacent
    Local
    Physical
    Privileges Required
    None
    Low
    High
    User Interaction
    None
    Required
    Scope
    Unchanged
    Changed
    Confidentiality
    None
    Low
    High
    Integrity
    None
    Low
    High
    Availability
    None
    Low
    High